How to use the Insulation Accessories insulating rod:
① The insulating rod must be used within the validity period.
② When there is no tester of the corresponding level, the insulating rod can be used for testing. Insulating gloves and insulating shoes must be worn.
③ How to use the insulating rod to test electricity: Stand in a good position and stand firmly, then lift the metal head of the insulating rod close to the equipment to be tested. When it is close to virtual connection, watch the sparks and listen to the discharge sound. If there are sparks and crisp discharge sounds, it is charged. If it is not certain, the metal head of the insulating rod can be connected to the charged body, and gently slide along the surface of the charged body to observe whether there are small sparks and discharge sounds. If there are, it is charged, otherwise it is not charged.
④ Method of using an insulating rod to hang the ground wire: first connect the grounding end of the ground wire, put the metal T-end of the insulating rod into the metal ring of the ground wire terminal to clamp the ground wire end, tighten the ground wire along the insulating rod, lift the ground wire close to the equipment that has been proven to be without electricity, touch the three phases respectively, and after fully discharging, quickly and accurately hang it on one phase, use the insulating rod to pull the ground wire head into the grounded wire, clamp it, and withdraw the metal T-end of the insulating rod. Then, continue to hang the ground wire of the next phase. 1V

How To Use The Insulating Pull Rod Of Power Fittings

Next Precautions When Using The Power Fittings Ground Resistance Tester