Suspension Wire Clamp Tilting Gear Suspension Wire Treatment Measures
Due to the undulating terrain along the route of the transmission line, the unequal line span, and the changes in temperature, ice and other loads, the ground wires on both sides of the suspension point of the linear tower have different hanging angles (also called tilt angles). In places with large vertical spans, the hanging angle of the overhead line at the outlet of the hanging wire clamp may exceed the allowable value of the hanging wire clamp, causing the additional bending stress to increase, causing the overhead line to be damaged at the outlet of the wire clamp, causing broken strands or wires, so it is necessary to check the hanging angle of the overhead line to ensure that it does not exceed the limit. The hanging angle of the conductor occurs when there is a large arc sag. The hanging angle in work is generally the average of the hanging angles on both sides.
Insulation Piercing Connector The exit angle is the acute angle between the tangent direction of the arc at the outlet of the wire clamp and the center line of the wire clamp hull wire trough. It is related to the length of the wire clamp hull, the starting position of the arc, and the curvature radius R of the wire trough. When the conductor is suspended on the suspension clamp, due to the different spans and the height difference of the tower, the suspension angle of the conductor is variable, and the suspension angles of the conductors on both sides of the suspension clamp are not equal, which causes the clamp to deflect on the vertical plane relative to the insulator string. Wire suspension angle - the acute angle θ between the tangent direction of the arc at the contact point between the conductor and the outer side of the clamp and the horizontal line. When the clamp is in a horizontal position, the outlet angle of the clamp is equal to the conductor suspension angle.
When the result does not meet the required value, the measures that can be taken are to adjust the tower position or tower height to reduce the height between the two suspension points, thereby reducing the suspension angle of the suspension clamp on one or both sides to reduce the use tension of the conductor in the tension section, that is, to relax the wire; or use a suspension clamp with a larger suspension angle; or use a double suspension clamp; use pre-interlaced wire protection wire, etc.