What are the requirements of line fittings for the location of installing ground wires?
Insulation Piercing Connector What are the requirements for the location of installing grounding wires?
A grounding wire must be installed between the power-off equipment and the live equipment that may supply power to the power-off equipment, or on the power-off equipment that may generate induced electromotive force. The distance between the grounding wire and the live part should meet the safety distance requirements to prevent accidents caused by swinging and discharge between the live part and the grounding wire. When inspecting the busbar, the number of grounding wires should be determined according to the length of the busbar and the actual situation of whether there is induced electromotive force. Only one set of grounding wires can be installed for inspecting busbars below 10m. When inspecting the line side of the gate-type structure, if the distance between the work location and the installed grounding wire is less than 10m. Even if the work location is outside the grounding wire, no additional grounding wire will be installed. If the inspected equipment is several parts that do not want to be connected electrically. Then all parts should be equipped with grounding wires. The grounding wire should be hung where the staff can see it, but it must not be hung in front of the staff to prevent the staff from being burned when the power is suddenly on.