What Safety Measures Should Be Taken When Working On The Secondary Circuit Of A Live Power Fitting Current Transformer?

Publish Time: Author: Site Editor Visit: 8

What safety measures should be taken when working on the secondary circuit of a live Changeover load isolationg switch current transformer?
(1) It is strictly forbidden to open the secondary side of the current transformer (except for the photocurrent transformer).
(2) The secondary winding of the short-circuited current transformer must use a short-circuit plate or short-circuit line, and it is strictly forbidden to wrap it with wires.
(3) When performing any work on the circuit and wire between the current transformer and the short-circuit terminal, strict safety measures should be taken and a secondary work safety measures form should be filled out.
(4) It is forbidden to disconnect the permanent grounding point of the circuit during work.
(5) When working, there should be a dedicated person to supervise, use insulating tools, and stand on insulating pads.